The valve will operate correctly within the following temperature conditions;
The following are clearly visible
120,000 BTU/Hr
Minimum static bursting pressure > 6.5 Mpa (65 bar), reached through a gradual pressure increase spread over 20 seconds starting from atmospheric pressure.
With a minimum of 5 full threads engaged, the inlet and outlet coupling threads do not strip or break when subjected to a tightening torque of 50Nm.
The stainless steels pass the salt spray fog test according to ASTM B 117 salt spray fog test. Stay time 100 hours. After having been dried in ambient temperatures, there are no rust spots present. A small yellow discolouration is acceptable.
Solenoid coil former and encapsulant are rated to UL94 – V0 and/or Glow wire-
IEC 695-2-1, 960° C
Solenoid assemblies are flash tested to 3.3 – 3.5kV ac, 50 Hz between earthed parts and live parts of opposite polarity.
The valve operates correctly between 0 Kpa and 6kPa at the inlet of the valve.
The valve is designed to comply with IEC730-2-8 clause 18.101.3
Flow established within 0.5 sec of power application
Within 0.5 sec after power is removed
Voltage |
Voltage | Frequency |
Power |
Holding |
Inrush |
Ambient |
Water |
Duty Cycle |
240Vac |
+10 / -10 |
50 |
8 |
56 |
83 |
135 |
80 |
continuous |
Voltage |
Voltage | Frequency |
Power |
Holding |
Inrush |
Ambient |
Water |
Duty Cycle |
120Vac |
+10 / -10 |
60 |
8 |
110 |
185 |
135 |
80 |
continuous |
Voltage |
Voltage | Frequency |
Power |
Holding |
Inrush |
Ambient |
Water |
Duty Cycle |
24Vac |
+10 / -10 |
50 |
8 |
490 |
560 |
135 | 80 | continuous |
Voltage |
Voltage | Frequency |
Power |
Holding |
Inrush |
Ambient |
Water |
Duty Cycle |
12Vdc |
+10 / -10 |
- |
8 |
1050 |
1050 |
135 |
80 |
continuous |
Voltage |
Voltage | Frequency |
Power |
Holding |
Inrush |
Ambient |
Water |
Duty Cycle |
9VDc Latching |
-3V / +3V |
- |
11 |
1200 |
1200 |
135 |
80 |
continuous |